CG-460-1560 Hydrolevel CycleGard Low Water Cut-Off With 15 Second Delay 120V
Part #HYDCG4501560
MFG #45-460-1560
Manufacturer Name : Hydrolevel
- Boiler Low Water Cut-Off
- Item Low Water Cut-Off
- Type Probe
- Applicable Standard UL
- Actuation Type Automatic
- Switch Type SPDT
- Input Supply Rating 120 Volt AC
- Pressure Rating Maximum 15 PSI (Steam)
- Media Handled Steam
- Inclusions/Features Low Water Indicating Light
- Application Residential/Commercial
- Switching Capacity 5.8 Amp (Full Load), 34.8 Amp (Locked Rotor)
- Power Consumption 4.2 VA
- Cyclegard Continually Monitors the Boiler Water Level Like other Probe Type Cut-Offs; Uses Intermittent Level Test (Lit) Technology to Provide Protection Against False Signals Created by Foaming and Volatile Water Conditions in the Boiler; Lit Periodically Removes Power from the Burner Circuit; During This Test, Foam Dissipates and the Water Level Stabilizes Allowing Cyclegard to Monitor the True Water Level in the Boiler; The Superior Protection of Cyclegard has Made it the Standard Low Water Cut-Off for Many of the Industry's Leading Boiler Manufacturer; Burner Circuit Contacts Open After 15 Second Delay in a Low Water Condition; Delay Prevents Short Cycling Caused by Momentary Fluctuations in the Boiler Water Level; Automatically Reactivates Burner Circuit 30 Seconds After Water Reaches the Probe, Allowing Optional Water Feeder to Raise Water Level Above the Probe; Perform the Lit Every 10 Minutes for 90 Seconds